Off-grid planning

Off-grid solar in winter: sizing for low sun, cold and snow

An off-grid system has to work in its worst month, not its average one. Here is how winter changes panels, batteries and backup power.

The short version: size your array with your location's December sun hours, give the battery enough days of autonomy for winter storms, keep lithium batteries above freezing while charging, check panel voltage at your coldest temperature, tilt steeply for snow, and plan a generator for long dark stretches.

At a glance

Sized for summer (5 sun hrs)2 panels
Sized for December (2.5 sun hrs)4 panels
Don't charge LiFePO4 below32°F / 0°C
Winter panel tiltLatitude + 15°

Why winter is the hard month

Winter checkpoints, from roof to outlet
  1. PanelsTilt steeply; clear snow safely
  2. Charge controllerCheck cold-morning voltage
  3. BatteryKeep above freezing to charge
  4. Inverter/chargerGenerator plugs in here
  5. Cabin loadsPropane or wood for heat

The generator is a backup input, not part of the chain: it connects to the inverter/charger, which uses it to recharge the battery and run loads during long dark stretches.

Size the array for your worst month

The array size depends directly on peak sun hours. Here is the same small cabin (the off-grid planner's essential loads: a fridge, lights, internet and a water pump, 2.55 kWh a day) sized with 400 W panels at different sun-hour values.

400 W panels needed as sun hours drop
  • 5 sun hours/day0.8 kW array2 panels
  • 4 sun hours/day1.2 kW array3 panels
  • 3 sun hours/day1.6 kW array4 panels
  • 2.5 sun hours/day1.6 kW array4 panels
  • 2 sun hours/day2.0 kW array5 panels
  • 1.5 sun hours/day2.8 kW array7 panels

A cabin sized on a typical 5-hour annual average gets 2 panels. If December only delivers 2.5 hours, it needs 4. Find your monthly values with NREL's PVWatts calculator, then enter the lowest month you need to run on solar into the planner's "Peak sun hours" setting.

Add battery days for winter storms

Days of autonomy is how long the battery can run your loads with no sun. Summer cabins often get by with one or two; winter use usually needs more, or a generator. For the same cabin:

Advertised LiFePO4 battery for the same cabin
  • 2 days of autonomy7.65 kWh
  • 3 days of autonomy11.48 kWh
  • 5 days of autonomy19.13 kWh

Battery cost climbs quickly. Past two or three days, a generator is usually the cheaper way to cover the rare long storm. See the battery sizing guide for the full calculation.

Try it

See how winter changes your system

What do you want to keep running?
Panels you need4 × 400 W1.6 kW array. Scale: 0–12 panels.
Daily use
2.55 kWh
Battery (2 days)
7.65 kWh
Inverter
1,232 W
Startup surge
1,735 W

Uses the same math as the off-grid planner at 2.5 peak sun hours. A planning estimate, not a design.

Keep batteries warm enough to charge

Check panel voltage on the coldest morning

Panels produce higher voltage when they are cold. A typical panel's open-circuit voltage (Voc) rises about 0.25–0.3% for every °C below 25°C, so at -20°C it can be roughly 11–14% above the label value. That combined string voltage must stay under your charge controller's maximum PV input, or the controller can be damaged on a clear, frigid morning.

Panel Voc × panels in series× (1 + Voc temperature coefficient × (record low °C − 25°C))= must be below the controller's max PV voltage

Enter the coefficient exactly as the datasheet lists it, as a negative number such as −0.28%/°C (−0.0028). With a record low below 25°C, the two negatives multiply to a positive, so the result is higher than the label Voc, as it should be. If your answer comes out lower than the label Voc, a sign is wrong.

Example: two panels with a 40 V Voc in series, a −0.28%/°C coefficient, and a −25°C record low: 80 V × (1 + (−0.0028 × (−25 − 25))) = 80 V × 1.14 = 91.2 V. That fits a 100 V charge controller, but three panels in series (136.8 V) would need a 150 V controller. Many controller makers also publish string-sizing calculators.

Plan for snow and tilt

Reduce winter loads

Plan generator backup

An inverter/charger lets a generator recharge the batteries and run loads at the same time. Size the generator to cover your charger's input plus any loads running while it charges, and keep it outdoors, away from windows, with a working carbon monoxide alarm inside. Connecting a generator to a building's wiring requires a transfer switch installed by an electrician.

FAQ

Do solar panels work in winter?

Yes. Cold actually makes panels slightly more efficient. The problem is fewer and weaker sun hours, a low sun angle, and snow cover, so a system sized on annual averages comes up short in December.

How many peak sun hours do I get in winter?

It depends on latitude and weather. Many northern and mountain locations get a fraction of their summer sun hours in December. Look up your own monthly values with NREL's PVWatts calculator and size for the lowest month you need to run on solar.

Can I charge a LiFePO4 battery below freezing?

Not safely. Charging lithium iron phosphate below about 32°F (0°C) can permanently damage it. Use a battery with low-temperature charge protection plus self-heating, or keep it in an insulated, heated space.

Should I tilt my panels steeper in winter?

A tilt of roughly your latitude plus 15° favors the low winter sun and helps snow slide off. Adjustable ground mounts let you change tilt by season.

Do I need a generator for an off-grid cabin?

For year-round winter use it's strongly recommended. A generator covers multi-day storms for far less than the extra panels and batteries needed to ride them out on solar alone.

Next, check that your inverter can start winter loads like a well pump with the inverter sizing guide.